Solutions by market

Critical Environments

Laboratories, healthcare procedure spaces and cleanrooms run once-through: nothing returns, everything is exhausted, and the entering outdoor air sets the sensible heat ratio. Viking OA is selected at that condition and holds a supply dewpoint as low as 43°F without overcooling the space to get there.
The challenge

The challenge in this building type

When every cubic foot of supply is outdoor air, the space load is no longer the design point. At 95°F DB / 78°F WB the latent fraction of the entering air exceeds anything a recirculating system was selected for, the pressurization cascade has to hold through every door cycle, and the exhaust stream often cannot be recovered through a wheel.

Once-through changes the math

With no return air, the entering condition is the outdoor air. Selection at 95°F DB / 78°F WB and an SHR of 0.70 or below is the only honest design point.

Reheat is not optional

Holding dewpoint without overcooling the room requires reheat at the unit. Terminal reheat that exists only to correct overcooling is energy spent twice.

The pressure cascade

Clean to less clean, through door cycles and exhaust changes. Supply has to be reset against exhaust flow and space differential pressure, continuously.

Classified exhaust

Fume, isolation and process exhaust cannot pass through an energy wheel. Recovery is applied only where the exhaust stream permits it, and excluded where it does not.

Systems

Recommended systems

The KCC equipment that fits this building type, and the roof interface it lands on.

PRIMARY RECOMMENDATION

Viking OA

Tight-band dewpoint control with modulating hot-gas reheat, static-pressure reset against exhaust, N+1 by cabinet count. Stainless interiors, all-stainless or all-copper coils, chilled-water coils with turbulators against a campus plant, UV on the leaving side of the coil and a 6-inch rack for high-efficiency final media.
PAIRED SYSTEM

Viking HA

The mixed-air platform for the recirculating spaces on the same campus: offices, support areas and administration, on the same cabinet construction and controls.
ROOF INTERFACE

Curbs & adapters

Structural curbs and adapters to the unit footprint, plus smoke vents, roof hatches and walkways from the same source, over structure coordinated to the pound. Details in IOM-A001 before the lift.
Codes & Compliance

Codes & compliance

ASHRAE 170

Ventilation of health care facilities: once-through supply at a controlled dewpoint, pressure relationships held by fan reset against exhaust.

ANSI/AIHA Z9.5 · ISO 14644

Laboratory ventilation and cleanroom classification: 100% outdoor air with no recirculation, filtration staged to the classification.

ASHRAE 62.1 / 90.1

Controlled ventilation delivery; energy recovery applied where the exhaust stream permits and excluded where it does not.

AHRI 920

Certified DX-DOAS performance under ASHRAE SSPC 198, the method of test KCC engineers helped write.

PROJECT PROOF
Named project, named outcome

One-line result with a number in it. Every vertical page carries at least one installed-performance proof point.

FAQ

Frequently asked questions

What is a 100% outside air unit?

An air handling unit that supplies only outdoor air with no return or recirculation, used where the exhaust cannot be returned: laboratories, healthcare procedure spaces, cleanrooms and pharmaceutical suites. Because every cubic foot is outdoor air, the unit is selected at the outdoor condition rather than the space load.
By controlling the cooling coil to a leaving-air dewpoint and reheating the air with modulating hot-gas reheat to the discharge temperature the space needs. Viking OA holds a supply dewpoint as low as 43°F with a narrow deadband, so humidity control never drives the room temperature down.
Only where the exhaust stream is unclassified. Fume hood, isolation and process exhaust must not pass through an energy recovery wheel. Viking OA applies the total-energy wheel where the exhaust permits it; where it does not, recovery is excluded and KCC Applications Engineering reviews the alternative.
Stainless interiors, all-stainless or all-copper coils, eco-coated coil options, chilled-water coils with turbulators and a sine-wave coil where a campus plant is the design basis, and UV lights on the leaving-air side of the evaporator coil. All are specified at the unit as design special requests.
TALK TO KCC

One call to a rep who answers.

Exhaust classification, recovery applicability, pressurization strategy and construction packages are reviewed by KCC Applications Engineering with your local rep. One call.