With no return air, the entering condition is the outdoor air. Selection at 95°F DB / 78°F WB and an SHR of 0.70 or below is the only honest design point.
Holding dewpoint without overcooling the room requires reheat at the unit. Terminal reheat that exists only to correct overcooling is energy spent twice.
Clean to less clean, through door cycles and exhaust changes. Supply has to be reset against exhaust flow and space differential pressure, continuously.
Fume, isolation and process exhaust cannot pass through an energy wheel. Recovery is applied only where the exhaust stream permits it, and excluded where it does not.
The KCC equipment that fits this building type, and the roof interface it lands on.
Viking OA
Viking HA
Curbs & adapters
Ventilation of health care facilities: once-through supply at a controlled dewpoint, pressure relationships held by fan reset against exhaust.
Laboratory ventilation and cleanroom classification: 100% outdoor air with no recirculation, filtration staged to the classification.
Controlled ventilation delivery; energy recovery applied where the exhaust stream permits and excluded where it does not.
Certified DX-DOAS performance under ASHRAE SSPC 198, the method of test KCC engineers helped write.
One-line result with a number in it. Every vertical page carries at least one installed-performance proof point.
Exhaust classification, recovery applicability, pressurization strategy and construction packages are reviewed by KCC Applications Engineering with your local rep. One call.